Inspection #: 855573
Inspection Type: FirePumpFinal
Inspector: B.Meinhardt
Result: Partial
Comment: Sam Betker is the onsite contact and his phone number is 907-306-0423. If possible we would like to do this inspection sometime around 10:00am. Thanks Kenny Requested by: Kenneth Yates 9072308624 kenny@chinookfire.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
11/21/2025TransferFirePumpFinal10Install Cert<div>Provide Installation Certification and test report.</div><div><br></div> Provide install cert.
11/21/2025TransferFirePumpFinal2CCO ApprovedCCO Approved for Fire Pump Need to complete fire alarm interface to fire pump controller.
11/21/2025TransferFirePumpFinal6Correction(s) #1<div>Correct the following item(s):</div><div><br></div> Need to complete fire alarm interface to fire pump controller.
11/21/2025TransferFirePumpFinal5Factory Test CurveProvide factory test curve for fire pump Provide Factory test curve and field test curve.&nbsp; &nbsp;
11/21/2025TransferFirePumpFinal4Fire Pump Operational TestFire pump NFPA 20 commissioning test approve Fire pump operational test complete with Factory Rep.