Inspection #: 855440
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: Please call 30min ahead thanks Requested by: Vasiliy M 907-671-7275 Vasiliy@vannoyelectric.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/29/2025TransferCorrect Below*  1. permanent labeling for disconnect required 2. Install numbers at panels 3. AFC and date required at panels. 4. Unique labeling for furnaces required at panel schedule. 5. Post sheet E0.3 at panel locations designating hazardous locations. 6. Duct seal raceways from passage of air and condensation between interior and exterior.
10/29/2025TransferCorrect Below* Detectors.1. Per the detector literature. Detectors are for detection of Carbon monoxide and natural gas. Detectors do not appear to be for the gas that is intended top be detected. Engineer required to determine correct detector for application and submit documentation. 2. Recommended locations of detectors requires that they are placed away from air vents. Currently they are all closely mounted to the air vents for each unit. Engineer to determine correct detector and placement of.