Inspection #: 855235
Inspection Type: Fire Alarm Final
Inspector:
Result:
Comment: C Wing 2nd Floor Rooms and Corridor. C Wing West Stairwell. Brian - 907-205-9771 Requested by: Stephanie 907-336-5000 gmwservice@gmwfire.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/27/2025 Firealarm20Correction(s) #7<div>Correct the following item(s):</div><div><br></div> Rename smoke locations, Smoke 2166 needs to be 2168 and smoke 2194 needs to be next to room 2198.&nbsp;
5/20/2025 firealarm11Fire Alarm approved CCOFire Alarm approved for CCOBldg C, 3rd floor rooms, Corridors & NW stairsokay to proceed.<div><br></div><div>* CCO for fire alarm 2nd floor and west stairs approved on 6/27/25</div>
4/14/2025 firealarm11Fire Alarm approved CCOFire Alarm approved for CCO2nd & 3rd floor commercial Area and elevator recall. 1st floor commercial sideCO approved for 1st floor commercial side. Excluding brewery/ tasting room and elevator lobby area.&nbsp;
2/21/2025 Firealarm23Fire Alarm Notes 2Fire Alarm Notes: Building B phase 3 floors 1-3 approved for CO till 7/1/25. Zone list needs updates and verified at final inspection.&nbsp;
2/5/2025 Firealarm22Fire alarm Notes 1Fire Alarm Notes:3rd floor, 2nd floor commercial areas& elevator 3 recall.All areas worked as required, okay for C.C.O. until 7/1/25
1/10/2025 Firealarm14Correction(s) #1<div>Correct the following item(s):</div><div><br></div> Note: Elevator needs to be recalled to alternant floor and flash red hat when heat detector in pit is tripped.&nbsp;
8/9/2024 firealarm11Fire Alarm approved CCOFire Alarm approved for CCO Fire alarm approved for 3rd floor all rooms for phase 2<div>and&nbsp;<span style="color: rgb(0, 0, 0); font-family: Arial; white-space-collapse: preserve;">Remainder of 1st Floor Rooms, and Corridor A Wing Residential, 2nd and 3rd Floors till 7/1/25.</span></div>
8/9/2024 Firealarm22Fire alarm Notes 1Fire Alarm Notes: All rooms verified working on 1st through 3rd for low frequency phase 1 and 2<span style="color: rgb(0, 0, 0); font-family: Arial; white-space-collapse: preserve;"> and Corridor A Wing Residential, 2nd and 3rd Floors </span>for voice with low frequency.