| Date | Status | Code | Description | Ref | Location | Comments |
| 5/16/2025 | Transfer | Correct Below | * | | | 1. Label RTU disconnects with source.
2. EM system incomplete.
3. Fault current on drawings does not match labels on panels.
4. Label all panels with available fault current and date calculated.
5. PRO-CUT equipment does not appear to be listed and requires a field evaluation from a licensed NRTL.
6. Emergency egress head at main entrance incomplete. |
| 5/16/2025 | Transfer | Correct Below | * | | | |