Inspection #: 854865
Inspection Type: Final Electrical
Inspector: O.Burbridge
Result: Correction
Comment: Electrical final approved conditionally until 8/1/25 pending completion of noted items.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/16/2025TransferCorrect Below*  1. Label RTU disconnects with source. 2. EM system incomplete. 3. Fault current on drawings does not match labels on panels. 4. Label all panels with available fault current and date calculated. 5. PRO-CUT equipment does not appear to be listed and requires a field evaluation from a licensed NRTL. 6. Emergency egress head at main entrance incomplete.
5/16/2025TransferCorrect Below*   