| Date | Status | Code | Description | Ref | Location | Comments |
| 5/16/2025 | Transfer | Correct Below | * | | | 1. Label RTU disconnects with source.
2. No power at several exit signs and remote heads. |
| 5/16/2025 | Transfer | Correct Below | * | | | EMS system incomplete. |
| 5/14/2025 | Transfer | Correct Below | * | | | 1. Provide updated MOA reviewed drawings reflecting work done on site.
2. Available fault current on drawings does not reflect labeling on panels.
3. Label available fault current and date calculated on all panels.
4. Break room seismic wires required for light fixtures.
5. Need access to rooftop and lid above break room.
6. Demo MC cable and box behind bathrooms.
7. Blank off receptacles at power poles.
8. Need access to transformer.
9. Label top of transformer to indicate no storage.
10. Pro-cut equipment does not appear to be listed.
|