Inspection #: 854444
Inspection Type: Final Electrical
Inspector: O.Burbridge
Result: Correction
Comment: Final inspection please. Brett will be on site. 907-440-1142 Requested by: Dave 907-349-9668 dhouse@ravenelectric.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/20/2026TransferCorrect Below*  1. Reactor cabinet and blower controller cabinets do not appear to be listed and will require field evaluations. 2. Bonding bushing required at transformer disconnect. 3. EM light in tunnel has no power. 4. Bond around water meter. 5. Monument sign must be fed with single multiwire branch circuit or have a panel that subfeeds the 3 circuits on the sign. 6. Labeling required per 210.5(C)(1). 7. Bathroom heater incomplete.