Inspection #: 854258
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: Progress inspection. See corrections identified.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/1/2025TransferCorrect Below* MDP-aAlternate source interconnect location on plans shows connection at opposite end from normal source. Does not appear to be at this time. Labeling required for this connection. As well as 705.12 (B)(3)(2) for alternate source.
8/1/2025TransferCorrect Below* MDP-AOne line shows 1200 amp OCPD. main appears to be 2000 amp.
8/1/2025TransferCorrect Below*  Panels in lower level electrical room need labeling for panel designation and AFC/date. labeling required at shunt trips per E.04. and for alternate sources at service equipment.
8/1/2025TransferCorrect Below*  MDP-A: drain pipe in working clearance near floor of equipment.
8/1/2025TransferCorrect Below* Cap off unused raceways at future capstones.  
5/13/2025TransferCorrect Below* Phase 33 pendant lights incomplete. Fireplace incomplete.
4/30/2025TransferCorrect Below*  Kitchen coffee maker incomplete.