| Date | Status | Code | Description | Ref | Location | Comments |
| 6/4/2025 | Transfer | PlumbFinal | Comments | See Inspector Comments | Shower/Tub Valve (bathroom) | Shower/tub thermostatic mixing valve not tested for temperature. |
| 5/6/2025 | Corrected | PlumbFinal | Comments | See Inspector Comments | Natural Gas UG Meter to Reg | UG Natural Gas tubing damaged at regulator connection. Repair and test with 60psi, per 2018 UPC Section 1213.3. |
| 5/6/2025 | Corrected | PlumbFinal | Comments | See Inspector Comments | Bathroom WC and Tub | Joints between fixture and wall or floor to be made water-tight (caulked) per 2018 UPC Section 402.2 |
| 5/6/2025 | Corrected | PlumbFinal | Comments | See Inspector Comments | Kitchen Sink Tailpiece | Sink tailpiece corrugated PVC. Not listed approved for installation. Replace with approved slip coupling extension. |
| 5/6/2025 | Corrected | PlumbFinal | Comments | See Inspector Comments | Bathroom Lav Drain | Lavatory drains through illegal unvented S-trap. Prohibited per 2018 UPC Section 1004.1 Install vent to serve fixture. |
| 5/6/2025 | Corrected | PlumbFinal | Comments | See Inspector Comments | Dishwasher Air Gap | Install dishwasher air gap fitting in accordance with 2018 UPC Section 414.3 |
| 5/6/2025 | Corrected | PlumbFinal | Comments | See Inspector Comments | WH Drainage Pan | Install drainage pan in accordance with 2018 UPC Section 507.5 |
| 5/6/2025 | Transfer | PlumbFinal | Comments | See Inspector Comments | WH T&P Discharge Piping | No discharge piping installed. Install approved material pipe to discharge into approved location for appliance Per 2018 UPC Section 608.5 |