| Date | Status | Code | Description | Ref | Location | Comments |
| 5/7/2025 | | MechFinal | See comments | See Inspector Comments | Water Heater Enclosure | No combustion air for appliance enclosure. Combustion air opening shall directly communicate with the outdoors and shall be no less than 3" diameter per 2018 IMC Section 304.5.3.1 and 304.6.2. |
| 5/6/2025 | Transfer | MechFinal | See comments | See Inspector Comments | WH Enclosure | Appliance draft hood not attached. Fasten in accordance with install guide instruction. |
| 5/6/2025 | Transfer | MechFinal | See comments | See Inspector Comments | FAF Closet | FAF return grill blocked by closet door. Remove obstruction in accordance with manufacturer's installation instruction. |
| 5/6/2025 | Transfer | MechFinal | See comments | See Inspector Comments | Bath exhaust fan termination | Fan termination requires 1/4" screen per 2018 IMC. |
| 5/6/2025 | Transfer | MechFinal | See comments | See Inspector Comments | Bathroom | Bath fan not operational |
| 5/6/2025 | Transfer | MechFinal | See comments | See Inspector Comments | | Range hood not operational |