Inspection #: 852698
Inspection Type: Service
Inspector: O.Burbridge
Result: Correction
Comment: 1200A Disconnect and Transformer for Micro turbines. Please call 20 minutes prior to inspection. Requested by: Dylan Berg 9073507114 dberg@superiorak.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/6/2025TransferCorrect service item below*  Please provide documented switching procedure for conversion to islanding mode for microturbines.
5/6/2025TransferCorrect service item below*  Please provide written approval from CEA for microturbine system interconnection.
5/5/2025TransferCorrect service item below*  Platform required at microturbine so that disconnect switch is not higher than 6'7".
5/5/2025TransferCorrect service item below*  Bond GEC from microturbines to MDP grounding system.
2/12/2025CorrectedCorrect service item below* Level 2 kitchenProvide consolidated plans with change order for this area detailing changes, to include load calcs with new or alternate equipment.
2/12/2025CorrectedCorrect service item below* level 2 dishwasherLarge dishwasher added (appears to be in excess of 100 amp). Does not appear to be on plans. Dishwasher that is shown on plans is 1800kva on equipment schedule, but does not appear to be on panel schedules on plans provided. Provide change order to include added load of equipment.
2/12/2025CorrectedCorrect service item below* level 2 kitchensignificant number of changes as it relates to circuit alteration. Provide consolidated change order with updated plans to inspect. Various circuits added, equipment moved to alternate circuits.
2/12/2025CorrectedCorrect service item below* Hood controlController requires 15 amp OCPD for this purpose. Note: not connected to a gfci or shunt trip OCPD.
2/12/2025CorrectedCorrect service item below* Level 2 Beverage station and kitchen.GFCI protection required per 210.8. Significant number of receptacles are not GFCI protected.
2/12/2025CorrectedCorrect service item below* Throughout, panel schedules incomplete, or missing.  
2/12/2025CorrectedCorrect service item below* Level 3 commercial kitchen 310. 1. Various receptacles require GFCI protection per 210.8. Will need to verify GFCI protection is readily accessible and not blocked by equipment or other means. 2. Equipment on schedules required to be onsite for inspection to verify listings and ratings.
2/12/2025CorrectedCorrect service item below* 3rd floor hallway bathrooms mirrors. Provide install instructions for connection. Wiring exposed with open conductors to mirror connections. Not an approved method. Fixed chapter 3 wiring method required to connect to mirrors.