Inspection #: 852116
Inspection Type: TempGas
Inspector: N.Jackson
Result: Correction
Comment: See Corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/16/2025TransferTempGas9See Comments below FAF Combustion Air (appliance enclosure and rooftop)Provide listed approved combustion air duct to appliance enclosure in accordance with manufacturer's installation instructions, and Section 304 of the 2018 IFGC.
5/16/2025TransferTempGas9See Comments below FAF Vent (appliance enclosure and rooftop)Replace vent, vent, connector, and roof termination cap serving FAF, for listed approved vent system in accordance with manufacturer installation instruction, and Section 503 of the 2018 IFGC.
5/16/2025TransferTempGas9See Comments below Natural Gas System Test (Exterior North Side)Test entire natural gas system downstream of pressure regulator with no less than 10 psi for 15 minutes 2018 UPC Section 1213.3.
5/16/2025TransferTempGas9See Comments below Range Gas Shutoff Valve (Kitchen)Each gas fired appliance shall be provided with a shutoff valve within 6' of the appliance served, in accordance with 2018 UPC 1212.6