Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 851876
Inspection Type: Mechanical Rough
Inspector: K.Hanson
Result: Partial
Comment: Partial Mechanical Rough - Approved To include the install of S & E/A ducting w/ related EFs serving all 2nd & 3rd fl Candlewood rms & corridor branch FDs serving 2nd & 3rd fls, OK to cover.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/25/2025TransferMechRghSee commentsSee Inspector CommentsHoliday inn side third floor. Supply air runs supply all rooms (32)Per 2018 IMC 607.3.3 actuator valves are required to have access panels large enough for maintenance, replacement, and service. DO NOT COVER.
2/25/2025TransferMechRghSee commentsSee Inspector CommentsHoliday inn side third floor fire and smoke dampers rooms 304, 324, and electrical room.Per 2018 IMC 607.3.3.2 Fire and smoke dampers must be installed and inspected to conform proper clearances are maintained for the functionality of its design. Per 2018 IMC 607.4 Access and identification, all smoke and fire dampers must be properly labeled and proper access provided for maintenance and replacement. Fire dampers are not installed and not inspected DO NOT COVER.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS