Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 850889
Inspection Type: Plumbing Rough
Inspector: J.Bean
Result: Partial
Comment: Plumbing Approved for install and test of approved flex's for heat and gas piping to Micro-Turbines

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/13/2025CorrectedPlumbRgh14CommentsSee Inspectors CommentsExterior Hydronic PipingPer 2018 IMC Section 1202.7 Flexible connectors, expansion are required from one structure to another, one pad to another pad. Per IMC Section 12.06.9 Stresses and Strains - Piping to be installed so as to prevent strains and stresses on piping
3/13/2025CorrectedPlumbRgh14CommentsSee Inspectors CommentsBasement Sump Pit (floor sink)Per 2018 UPC 710.3 thru 710.10 Listed sewage ejectors required to serve any approved receptors or floor drain. (Listed sewage ejector must be water tight) Note: Floor sink must be trapped when connected to permanent sewer. Note: Based on inspection and evaluation with installer grade can be achieved to gain elevation to tie into existing sewer main. Note: A field change order form could delete installation for the open sump pump.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS