Date | Status | Code | Description | Ref | Location | Comments |
4/9/2025 | | MechFinal | See comments | See Inspector Comments | The roof. | Per 306.5 Where equipment requiring access or appliances are located on an elevated structure or roof of a building, such access shall not require climbing over obstructions greater than 30" in height. Access to both the make up air unit and the RTU need a permanently affixed ladder or stairs. |
4/9/2025 | | MechFinal | See comments | See Inspector Comments | The roof. | Per the 2018 IMC 304.11, "Guards shall be provided where various components that require service and roof hatch openings are located within 10 feet of a roof edge or open side of a walking surface and such edge or open side is located more than 30" above the floor, roof, or grade below." Both the RTU, and the make up air require guards. |
4/9/2025 | | MechFinal | See comments | See Inspector Comments | The project. | Per the admin. code, prints shall reflect the work being performed. A deviation from the blue prints shall require a change order submitted to the MOA, approved and stamped by the plan reviewer. This stamped, approved, change order shall be on site at the time of inspection. The AC equipment for the "little sisters area" has been removed from the scope, therefore a change order is required. |