Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 849597
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Most corrections from 4/11/2025 resolved. The correction of GFCI protection for 3-phase kitchen mixers requires resolution as below.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/9/2025TransferCorrect Below* (2) 3-phase mixers.Engineer will need to verify sizing and show on drawings. Was not possible to see ratings on mixers.
7/9/2025TransferCorrect Below* Added 1-line items for 3-phase kitchen mixers.(2) mixers require a feeder from the 400A panel to a phase converter, buck / boost transformer, and 3-phase panel with 3-phase GFCI breakers. Engineer needs to verify installation and add to design with all appropriate calculations including AFC. Contractor will need to provide all required labelling.
4/11/2025CorrectedCorrect Below*  1. GFCI protection required for coffee maker and receptacles served by Rotary phase machine. 2. Labels required on service and panels. 3. Exterior lighting incomplete. 4. Bathrooms require GFCI protection for receptacles. 5. Secure liquidtight flex near junction box. 6. Verify gas and water bonds.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter