Inspection #: 849056
Inspection Type: Plumbing Rough
Inspector: J.Bean
Result: Partial
Comment: Partial Plumbing Approved for rough\test of dwv\water piping for rooms 1136 & 1138 and water mains. 4 shower valves approved, ok to cover. Corrections to be seen at later inspection

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/26/2025CorrectedPlumbRgh14CommentsSee Inspectors CommentsShowers (3)2018 UPC 408.7.5 Test for Shower Receptors. Shower receptors shall be tested for water tightness by filling with water to the level of the rough threshold. The test plug shall be so placed that both upper and under sides of the sub-pan shall be subjected to the test at the point where it is clamped to the drain.
9/26/2025CorrectedPlumbRgh14CommentsSee Inspectors CommentsRain Leader PipingCould not verify expansion joint. 2018 UPC 1101.5 Expansion Joints Required. Expansion joints or sleeves shall be provided where warranted by temperature variations or physical conditions.
9/26/2025TransferPlumbRgh14CommentsSee Inspectors CommentsWater PipingFlush Tank Toilets needing hammer arrestors. Will see hammer arrestors on angle stops at final. 2018 UPC 609.10 Water Hammer. Building water supply systems where quick-acting valves are installed shall be provided with water hammer arrestors. 2018 UPC MOA Amendment 609.10 Mechanical Devices. Examples of quick-acting valve locations include, but are not limited to, dishwashers, clothes washers, toilet ballcock, icemakers, and any single handle faucet.