| Date | Status | Code | Description | Ref | Location | Comments |
| 3/13/2025 | Transfer | PlumbRgh14 | Comments | See Inspectors Comments | Exterior Hydronic Piping | Per 2018 IMC Section 1202.7 Flexible connectors, expansion are required from one structure to another, one pad to another pad.
Per IMC Section 12.06.9 Stresses and Strains - Piping to be installed so as to prevent strains and stresses on piping |
| 3/13/2025 | Transfer | PlumbRgh14 | Comments | See Inspectors Comments | Basement Sump Pit (floor sink) | Per 2018 UPC 710.3 thru 710.10 Listed sewage ejectors required to serve any approved receptors or floor drain. (Listed sewage ejector must be water tight) Note: Floor sink must be trapped when connected to permanent sewer. Note: Based on inspection and evaluation with installer grade can be achieved to gain elevation to tie into existing sewer main.
Note: A field change order form could delete installation for the open sump pump. |