Inspection #: 846360
Inspection Type: Final Fire Inspection
Inspector: B.Meinhardt
Result: Correction
Comment: 3rd floor only Requested by: TJ Leaman 2089853899 tleaman@UnitCompany.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/21/2025TransferFire 15Correction(s) #2Please correct the following: Fire rated double doors are removed between the commercial and residential areas on the 3rd floor.   Replace doors and have structural and fire reinspect.  
3/21/2025TransferFire 13Correction(s) #1Please correct the following: Door to fire rated stairwell to the east does not close and latch on 3rd floor.
3/21/2025TransferFire 16Correction(s) #3Please correct the following: 3rd floor commercial sprinkler protection.   Multiple sprinkler heads are painted, sprinkler heads in slatted ceiling are void of the listing as they do not have a listed escutcheon ring installed for semi recessed installation, conference room needs sprinkler head installed in breakfast bar area, beer tap area needs sprinkler head installed - area has closet doors to enclose, need to look at all heads that they are parallel to ceiling.  This is not a complete list.