Click Here To View Another Inspection Inspection #: 845785 Inspection Type: Underground Plumbing Inspector: Y.Dovba Result: Partial Comment: Underground rain-leader piping rough-in and tests Approved. (Shallow piping). NOTE: Per 2012 local amendment 314.4 please use clean fill and protect piping through slab. NOTE: Per 2012 UPC section 707.4 Install clean-outs at upper terminals above slab when horizontal runs exceed 100 ft and change of direction of 135 degrees takes place. Inspection Corrections DateStatusCodeDescriptionRefLocationComments