Inspection #: 844389
Inspection Type: Fire Rated Wall(s)
Inspector: J.Sooter
Result: Partial
Comment: Discussed penetrations through wrapped beams for sprinkler piping. Penetrations are shown on approved plans. Contractor verified with the architect and provided applicable UL listed assembly WL 2128. This is acceptable.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/6/2025TransferFIREWALLCSee Inspector commentsInspector commentsLaundry room shaft on level 1. Firestop gaps in framing to provide continuous required rating from 1" shaft liner out to flange to be installed on face of shaft.