Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 843096
Inspection Type: Mechanical Rough
Inspector: K.Hanson
Result: Correction
Comment: Partial Mechanical Rough - Approved To include The install of S & R/A branch & main ducting serving Holiday 3rd fl corridor & FSD install related to rms 304 & 324, S & E/A ducting w/ related FSDs serving rms 453, 468 & 476, OK to cover. See corrections. NOTE: 3rd fl corridor mains near Mech rm, Mech rm, rms 337 & 339 incomplete.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/3/2025TransferMechRgh2Provide FSD Install GuideProvide fire/smoke damper installation instructions IMC 607.2  
2/25/2025TransferMechRgh23 Previous inspection items have not been correctedHoliday inn side third floor fire and smoke dampers mech/electrical room.Per 2018 IMC 607.3.3.2 Fire and smoke dampers must be installed and inspected to conform proper clearances are maintained for the functionality of its design. Per 2018 IMC 607.4 Access and identification, all smoke and fire dampers must be properly labeled and proper access provided for maintenance and replacement. Fire dampers are not installed and not inspected DO NOT COVER.
2/25/2025CorrectedMechRgh23 Previous inspection items have not been correctedHoliday inn side third floor. Supply air runs supply all rooms (32)Per 2018 IMC 607.3.3 actuator valves are required to have access panels large enough for maintenance, replacement, and service. DO NOT COVER.
2/25/2025CorrectedMechRghSee commentsSee Inspector CommentsLeft blank.Disregard, cannot delete correction tab.