| Date | Status | Code | Description | Ref | Location | Comments |
| 3/12/2025 | Transfer | Correct Below | * | | | Update panel labeling to indicate source of power and available fault current/date calculated. |
| 3/12/2025 | Transfer | Correct Below | * | | | Kitchen equipment incomplete. Complete kitchen or submit change order to remove kitchen equipment from drawings. |
| 2/19/2025 | Corrected | Correct Below | * | | RTU-1 | Fault current shows excess of 10k AFC at RTU-1, unit AIC rated for 10K. Provide alternate method, or updated calculation detailing fault current. If other method used to remedy, detail on plans, labeling required at equipment. |
| 2/19/2025 | Transfer | Correct Below | * | | Level 3 deck equipment. | 1. Receptacle cover missing.
2. 15 amp OCPD required for exhaust fans.
3. Added fan for kitchen dish washer does not appear to be on plans. Change order required.
|
| 2/10/2025 | Corrected | Correct Below | * | | Level 3 conference rooms | Track heads incomplete. |