Inspection #: 842543
Inspection Type: Final Electrical
Inspector: O.Burbridge
Result: Correction
Comment: Rough in for west staff room wall and north MPR room wall approved. Electrical final for 3rd floor bar, elevator lobby and conference room approved. See corrections for kitchen.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/12/2025TransferCorrect Below*  Update panel labeling to indicate source of power and available fault current/date calculated.
3/12/2025TransferCorrect Below*  Kitchen equipment incomplete. Complete kitchen or submit change order to remove kitchen equipment from drawings.
2/19/2025CorrectedCorrect Below* RTU-1Fault current shows excess of 10k AFC at RTU-1, unit AIC rated for 10K. Provide alternate method, or updated calculation detailing fault current. If other method used to remedy, detail on plans, labeling required at equipment.
2/19/2025TransferCorrect Below* Level 3 deck equipment. 1. Receptacle cover missing. 2. 15 amp OCPD required for exhaust fans. 3. Added fan for kitchen dish washer does not appear to be on plans. Change order required.
2/10/2025CorrectedCorrect Below* Level 3 conference roomsTrack heads incomplete.