Inspection #: 842450
Inspection Type: Plumbing Rough
Inspector: N.Smith
Result: Correction
Comment: -Candlewood suites- west side - Water piping from in wall first floor up to rooms 351, 353, 355, 357, 359, 361, 363, 365, 367, 369, 371, and 375 tested and approved. OK to cover. NOTE: with the exception of hammer arrestors which can be installed and left exposed for later inspection.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/27/2025TransferPlumbRgh14CommentsSee Inspectors Commentsall quick acting valvesper 2018 UPC 609.10 water hammer. 609.10.1 water hammer arrestors required all throughout the building where quick acting valves are in place, such as toilet ballcock.