Date | Status | Code | Description | Ref | Location | Comments |
2/25/2025 | | MechRgh23 | | Previous inspection items have not been corrected | Holiday inn side third floor fire and smoke dampers rooms 304, 324, and electrical room. | Per 2018 IMC 607.3.3.2 Fire and smoke dampers must be installed and inspected to conform proper clearances are maintained for the functionality of its design.
Per 2018 IMC 607.4 Access and identification, all smoke and fire dampers must be properly labeled and proper access provided for maintenance and replacement.
Fire dampers are not installed and not inspected DO NOT COVER. |
2/25/2025 | | MechRgh23 | | Previous inspection items have not been corrected | Holiday inn side third floor. Supply air runs supply all rooms (32) | Per 2018 IMC 607.3.3 actuator valves are required to have access panels large enough for maintenance, replacement, and service. DO NOT COVER. |