Inspection #: 841576
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: See corrections. Electrical inspection for 3rd floor deck, and roof top.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/19/2025TransferCorrect Below* RTU-1Fault current shows excess of 10k AFC at RTU-1, unit AIC rated for 10K. Provide alternate method, or updated calculation detailing fault current. If other method used to remedy, detail on plans, labeling required at equipment.
2/19/2025TransferCorrect Below* Level 3 deck equipment. 1. Receptacle cover missing. 2. 15 amp OCPD required for exhaust fans. 3. Added fan for kitchen dish washer does not appear to be on plans. Change order required.
2/10/2025CorrectedCorrect Below* level 3 roof lighting. Verify correct circuit and function for egress lights.
2/10/2025TransferCorrect Below* Level 3 conference roomsTrack heads incomplete.
2/10/2025CorrectedCorrect Below* level 3 elevator lobby. Add a depth devices required.
2/10/2025CorrectedCorrect Below* Conference 308A and B.Projector connection/power incomplete. Verify compliance with use of flexible cord for connection.