| Date | Status | Code | Description | Ref | Location | Comments |
| 2/19/2025 | Transfer | Correct Below | * | | RTU-1 | Fault current shows excess of 10k AFC at RTU-1, unit AIC rated for 10K. Provide alternate method, or updated calculation detailing fault current. If other method used to remedy, detail on plans, labeling required at equipment. |
| 2/19/2025 | Transfer | Correct Below | * | | Level 3 deck equipment. | 1. Receptacle cover missing.
2. 15 amp OCPD required for exhaust fans.
3. Added fan for kitchen dish washer does not appear to be on plans. Change order required.
|
| 2/10/2025 | Corrected | Correct Below | * | | level 3 roof lighting. | Verify correct circuit and function for egress lights. |
| 2/10/2025 | Transfer | Correct Below | * | | Level 3 conference rooms | Track heads incomplete. |
| 2/10/2025 | Corrected | Correct Below | * | | level 3 elevator lobby. | Add a depth devices required. |
| 2/10/2025 | Corrected | Correct Below | * | | Conference 308A and B. | Projector connection/power incomplete. Verify compliance with use of flexible cord for connection. |