Click Here To View Another Inspection Inspection #: 841194 Inspection Type: Final Mechanical Inspector: K.Hanson Result: Correction Comment: Partial Mechanical Final - Approved To include the install of 1-S/A smoke damper serving VAV 1413 branch in corridor, 2-E/A smoke dampers serving rms 1435 & 1359, 1-E/A SFD serving women's restroom, S & R/A GRDs & flex serving phases 1 & 2, all on 14th fl, OK to cover. NOTE: Conference rm 1425 incomplete. Inspection Corrections DateStatusCodeDescriptionRefLocationComments 3/11/2025TransferMechFinal11FSD AccessibilityFire/smoke dampers must be accessible-IMC 607.4E & S/A SFDsAs per 2018 IMC 607.4 Access required.