Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 840058
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Partial
Comment: Electrical final conditionally approved until 2/6/25. See remaining correction.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/28/2025TransferCorrect Below* Kitchen/em lightingProvide change order for alternate egress lighting configuration.
1/28/2025CorrectedCorrect Below* OvenGFCI protection required per 210.8 and local amendment.
1/27/2025CorrectedCorrect Below* 15 amp max OCPD required for all circuits with SJTW cords installed to furniture with #14 awg cu conductors. See 400.5(A)(1).  
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS