Inspection #: 839880
Inspection Type: Electrical Rough
Inspector: E.Widman
Result: Correction
Comment: RTU-1, RTU-13, and Split units 1 and 2 Before commissioning them into use. Please call 30 minutes prior to arrival Requested by: Stephen Sink (701)590-6479 Ssink@fullfordelectric.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/3/2025Transfer01See inspection comments Roof topflat and level working clearances required to be maintained at roof top units. Some have ducting installed, some have gas piping in working clearances.
7/3/2025Transfer01See inspection comments Roof top.1. RMC required to roof top equipment.
1/27/2025Transfer01See inspection comments  1. Bollards required at transformers and panels. 2. Resupport vertically hanging raceways per NEC, or demo.
12/9/2024Transfer01See inspection comments  Provide change order with plan review for alternate equipment at service. Include Available fault current calculations for new panels and equipment.