Inspection #: 839875
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: Electrical final inspection for south area kitchen and sitting. See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/28/2025TransferCorrect Below* Kitchen/em lightingProvide change order for alternate egress lighting configuration.
1/28/2025TransferCorrect Below* OvenGFCI protection required per 210.8 and local amendment.
1/27/2025CorrectedCorrect Below* 15 amp max OCPD required for all circuits with SJTW cords installed to furniture with #14 awg cu conductors. See 400.5(A)(1).  