Inspection #: 839872
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: Electrical final conditionally approved until 2/15/25.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/27/2025CorrectedCorrect Below*  Update panel schedules.
1/27/2025TransferCorrect Below*  Provide plans that were shown onsite as a change order with plan review as it relates to available fault current and dates.
1/27/2025CorrectedCorrect Below*  Readily accessible GFCI protection required at various locations blocked by equipment or other, and elevated locations.