Inspection #: 839699
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: Progress inspection for North sitting side sitting area. See corrections. Ceiling rough approved. Some corrections from previous remain. Kitchen area and south sitting remain.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/27/2025 Correct Below* Luminaires in tables showing to be supplied with metal flex, or mc cable.  
1/27/2025TransferCorrect Below* 15 amp max OCPD required for all circuits with SJTW cords installed to furniture with #14 awg cu conductors. See 400.5(A)(1).  