Inspection #: 839169
Inspection Type: Plumbing Rough
Inspector: J.Bean
Result: Partial
Comment: Plumbing Rough Approved for shower pan and shower pan test to include rooms 265-275, 277, 279, 281, 283, 285, 287, 289, 291, 293 295, 297, 299. Ok to Cover

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/20/2024TransferBackflowInspTested and TaggedBackflow assembly shall be tested and properly tagged- UPC 603.4.2Irrigation BP 
6/20/2024TransferPlumbRgh9PlansApproved plans must be on site  
6/20/2024TransferGasPipeComSee comments Boiler gas pipingUnion fitting required downstream of boiler isolation valves to serve each boiler per 2018 IFGC.
6/20/2024TransferGasRgh14PipingSee commentssee commentsBoiler gas pipingUnion fitting required downstream of boiler isolation valves to serve each boiler per 2018 IFGC.