Click Here To View Another Inspection


Inspection #: 838820
Inspection Type: Sprinkler Hydrostatic Test
Inspector: D.Meneses
Result: Partial
Comment: 2nd floor Hydro test. Contact Steve @ 599-0208 to schedule. Requested by: Patrick Noblett 9075297702 patrick@accelfire.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/5/2025TransferFireSprkHydro2Partial Hydrostatic TestPartial approval for fire sprinkler system hydrostatic test for the following area(s):2nd floor onlyAll okay to proceed.
1/17/2025TransferFireSprkHydro2Partial Hydrostatic TestPartial approval for fire sprinkler system hydrostatic test for the following area(s):Penthouse & 1st floor boiler roomTested to 200+ PSI, all okay to proceed.
10/22/2024TransferFireSprkHydro2Partial Hydrostatic TestPartial approval for fire sprinkler system hydrostatic test for the following area(s):3rd and 4th floorTest to 200+ PSI all okay to proceed.