Inspection #: 838475
Inspection Type: Plumbing Rough
Inspector: E.Wood
Result: Partial
Comment: Shower pan liners and tests for rooms 371- 399 ( less room 378, it's a tub), Approved. OK to cover. Room 134 re-rough of the water supplies and demo of the tub/ shower valve,, and test, for a half bath, Approved. OK to cover.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/20/2024TransferBackflowInspTested and TaggedBackflow assembly shall be tested and properly tagged- UPC 603.4.2Irrigation BP 
6/20/2024TransferPlumbRgh9PlansApproved plans must be on site  
6/20/2024TransferGasPipeComSee comments Boiler gas pipingUnion fitting required downstream of boiler isolation valves to serve each boiler per 2018 IFGC.
6/20/2024TransferGasRgh14PipingSee commentssee commentsBoiler gas pipingUnion fitting required downstream of boiler isolation valves to serve each boiler per 2018 IFGC.