| Date | Status | Code | Description | Ref | Location | Comments |
| 2/11/2025 | Corrected | PlumbRgh14 | Comments | See Inspectors Comments | Indirect draining sinks & equipment in kitchen & bar areas | 1" air gap required to serve indirect draining sinks & equipment per 2018 UPC. |
| 2/11/2025 | Corrected | PlumbRgh14 | Comments | See Inspectors Comments | Steamer kettle, steam oven & espresso machine in kitchen & coffee shop | Vented dual check ASSE 1012 required to serve all seam producing equipment per 2018 UPC & Cross Connection Control Manual. |
| 1/10/2025 | Corrected | GasPipeCom | See comments | | Gas regulators | As per 2018 IFGC 410.2 note 6 downstream tee fitting shall be installed no less than 10 pipe diameters from regulator. |