Inspection #: 838281
Inspection Type: Plumbing Rough
Inspector: K.Hanson
Result: Correction
Comment: Partial Plumbing Rough - Approved Too many incomplete items throughout job to note, see corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/11/2025CorrectedPlumbRgh14CommentsSee Inspectors CommentsIndirect draining sinks & equipment in kitchen & bar areas1" air gap required to serve indirect draining sinks & equipment per 2018 UPC.
2/11/2025CorrectedPlumbRgh14CommentsSee Inspectors CommentsSteamer kettle, steam oven & espresso machine in kitchen & coffee shopVented dual check ASSE 1012 required to serve all seam producing equipment per 2018 UPC & Cross Connection Control Manual.
1/10/2025CorrectedGasPipeComSee comments Gas regulatorsAs per 2018 IFGC 410.2 note 6 downstream tee fitting shall be installed no less than 10 pipe diameters from regulator.