Inspection #: 836574
Inspection Type: Ceiling Rough Electrical
Inspector: O.Burbridge
Result: Partial
Comment: B2 corridor lid and C2 bathroom rough in approved.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/19/2024CorrectedEC1Correct Below 2nd Floor B wing ceilingSouth end of ceiling has open junction boxes.
12/19/2024CorrectedEC1Correct Below 2nd floor C wing bathrooms on west endCut up pieces of sheet metal studs do not qualify as nail plates. Nail plates must be 16 gauge steel.