Click Here To View Another Inspection Inspection #: 833999 Inspection Type: Electrical Inspection Inspector: M.Green Result: Approved Comment: Fire pump controller one-for-one replacement to existing fire pump complete and approved. IMPORTANT NOTES: 1. Existing pump served by the replacement controller is an NEC 695 fire pump per AFD, not a jockey pump. 2. Serialized matching of fire pump to controller is not being required by AFD. 3. Current NEC 695.3(F) and (G) requires transfer of power from normal source to generator to take place inside the fire pump room by means of a transfer switch listed for fire pump service. AFD is NOT requiring this for a one-for-one controller replacement. 4. All work took place inside the penthouse fire pump room. Did not investigate fire pump circuit protection from fire. Inspection Corrections DateStatusCodeDescriptionRefLocationComments