Inspection #: 833968
Inspection Type: Service
Inspector: E.Widman
Result: Partial
Comment: Service preinspect. Work ongoing. Grounding and bonding incomplete. Service OK to pre-wire.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/1/2025TransferCorrect service item below*  1. Verify and provide Full load current of pump to verify adequate OCPD protection of conductors for locked rotor current. 2. Lockable disconnect required for fire pump. See 695.4 (B)(3). 3. Ensure fire rated circuit for pump wiring within building.