Inspection #: 833966
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: Inspection for garage area and south upper and lower office areas. Electrical final conditionally approved for 30 days for areas noted. Corrections made for roof top units. Corrections made at panels related to working clearance at bollards.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/8/2026TransferCorrect Below* New panels. Provide plans detailing AFC and date for added panels. Label panels with AFC information to include date of calculation.
1/8/2026TransferCorrect Below* Fire pump room. Lighting shown to be battery backed em lighting. Currently not installed, standard lighting installed. Plans show 4 ea. in this area.
1/8/2026TransferCorrect Below* Garage area. GFCI protection required for all new receptacles per 210.8. Various locations throughout.