Inspection #: 832730
Inspection Type: Plumbing Inspection
Inspector: N.Jackson
Result: Correction
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
11/22/2024TransferPlmbCommentSee Commentssee commentsT&P Relief Discharge Pipe T&P discharge sch.40 BMI pipe threaded at terminal end. Per 2018 IMC Section 1006.6 Note 11) Safety and relief valve discharge shall not have a threaded connection at the end of such piping.
11/22/2024TransferPlmbCommentSee Commentssee commentsWater Heater Vent Vent missing gasket on second segment of vent pipe. Install additional gasket and provide install guide for vent system.