| Date | Status | Code | Description | Ref | Location | Comments |
| 11/14/2024 | Corrected | WaterHtrRpl2 | Relief Valve Termination | Relief valve discharge shall be 6" to 24" above finish floor or final grade - UPC local amendment 608.0 and UPC 608.5 | RELIEF VALVE PIPING | CURENTLY RELIEF VALVE PIPING IS RAN IN COPPER WITH A SECTION RAN IN PEX. PEX IS NOT LISTED FOR RELIEF VALVE PIPING. |