Inspection #: 831552
Inspection Type: Ceiling Rough Electrical
Inspector: O.Burbridge
Result: Correction
Comment: See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/19/2024TransferEC1Correct Below 2nd Floor B wing ceilingSouth end of ceiling has open junction boxes.
12/19/2024TransferEC1Correct Below 2nd floor C wing bathrooms on west endCut up pieces of sheet metal studs do not qualify as nail plates. Nail plates must be 16 gauge steel.
10/21/2024CorrectedEC1Correct Below 1st floor A wing corridorSupport communication wiring off of ceiling grid.
10/21/2024CorrectedEC1Correct Below 1st floor A wing corridorExit lights require seismic wires.