Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 829353
Inspection Type: Ceiling Rough Electrical
Inspector: O.Burbridge
Result: Cancel
Comment: Cancel- duplicate

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/21/2024TransferEC1Correct Below 1st floor A wing corridorSupport communication wiring off of ceiling grid.
10/21/2024TransferEC1Correct Below 1st floor A wing corridorExit lights require seismic wires.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS