Inspection #: 829191
Inspection Type: Ceiling Rough Electrical
Inspector: O.Burbridge
Result: Correction
Comment: Inspection for 1st floor A wing corridor: See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/21/2024TransferEC1Correct Below 1st floor A wing corridorSupport communication wiring off of ceiling grid.
10/21/2024TransferEC1Correct Below 1st floor A wing corridorExit lights require seismic wires.
8/5/2024CorrectedEC1Correct Below 2nd floor east sideJunction box for emergency lighting incomplete.
8/5/2024CorrectedEC1Correct Below 2nd floor east sideBond gutters with largest ground wire and provide covers and end caps.
8/5/2024CorrectedEC1Correct Below 2nd floor east sideReplace #12 conductors in flex between gutters and panels with #10 copper conductors and add #10 ground wire.