| Date | Status | Code | Description | Ref | Location | Comments |
| 8/15/2025 | Transfer | Firealarm27 | Correction(s) #12 | Correct the following item(s): | | Still need to test sprinkler flow switched, duct detection, isolator modules. Plan need to have instructions for smoke control on the panel. Descriptions for smoke control need to be clear and understandable for fire fighter use. Smoke control panel need to have key to turn on smoke control that will open all dampers and turn on fans with one operation. Smoke control panel need to have keys added for the stairwell pressurization system and to turn on ASU-1 (North Building) and ASU-2(South Building). Smoke control system operation generator. |
| 8/15/2025 | Transfer | firealarm2 | Install cert |
<p class="MsoNormal"><font face="Times New Roman">Provide Installation Certification and test report.</font></p>
| | Need to provide installers certification. |
| 8/15/2025 | Transfer | firealarm1 | Provide plans | Provide approved plans on site for inspection. | | No approved plans onsite during testing showing all the changes. |
| 8/15/2025 | Transfer | Firealarm26 | Correction(s) #11 | Correct the following item(s): | | Fire alarm rough in inspections on the smoke control wiring has not been accomplished as required on sheet FA103 of the approved drawings. |
| 8/15/2025 | Transfer | firealarm3 | Decibel report | Provide Decibel Level Report. | | Need to provide dBA report. |
| 8/15/2025 | Transfer | Firealarm25 | Correction(s) #10 | Correct the following item(s): | | AS-Built drawings need to be submitted as a change order for review and approval. |
| 8/15/2025 | Transfer | Firealarm24 | Correction(s) #9 | Correct the following item(s): | | Ground floor area B (FA104). (1) pull station in suite 190 exit has wrong description. (2) pull station M1-62 (L2) (3) Mixing clean room does not have a horn strobe installed, need to provide 2018 IFC 907.5.2.3.1 (4) Missing horn strobed in Image reading room, plans show it as just an office, need to provide 2018 IFC 907.5.2.3.1. |
| 8/15/2025 | Transfer | Firealarm21 | Correction(s) #8 | <div>Correct the following item(s):</div><div><br></div> | | Top of stairwell smoke on old system are part of the detection for the stairwell pressurization system and have not been replaced with new detection on the new fire alarm system. 2018 IFC 909.12.3 and 909.12.4 |
| 8/15/2025 | Transfer | Firealarm20 | Correction(s) #7 | <div>Correct the following item(s):</div><div><br></div> | | Lower level - Basement mechanical room heat detectors are 10+ feet below the ceiling. Heat detectors shall be mounted at the ceiling level. 2019 NFPA 72 Section 17.6.3.1.3.1. |
| 8/15/2025 | Transfer | Firealarm18 | Correction(s) #5 | <div>Correct the following item(s):</div><div><br></div> | | Duct detection has not been tested yet throughout the building. Basement ASU4 (Stariwell Pressurization) has an old duct detector existing the outside intake air supply that was not replaced. Basement ASU4 (Stariwell Pressurization) air discharge has a duct detector installed in only 1 of the 2 branches after is splits, add additional duct detection of relocate before it splits. |
| 8/15/2025 | Transfer | Firealarm17 | Correction(s) #4 | <div>Correct the following item(s):</div><div><br></div> | | Sprinkler system - There are 13 sprinkler flow switches in the programing, There are flow switches in the ground floor mechanical room, 5 story building on the 2nd west stairwell, 3rd floor just outside the west stairwell entrance, unknown other locations. It is unknown were the inspectors test are located to test these flow switches. Basement mechanical dry system low air pressure switch reports as High Air, alarm pressure switch reports as low air. Valve tamper switches need updated descriptions comply with 2018 IFC 907.6.3. |
| 8/15/2025 | Transfer | Firealarm19 | Correction(s) #6 | <div>Correct the following item(s):</div><div><br></div> | | Outside fire sprinkler bell rings on general alarm. Fire sprinkler bell only shall ring on sprinkler waterflow and be non sliceable until the water stops flowing. |
| 8/15/2025 | Transfer | Firealarm16 | Correction(s) #3 | <div>Correct the following item(s):</div><div><br></div> | | Device descriptions do not comply with the 2018 IFC 907.6.3 Initiating device identification. The fire alarm system shall identify the specific initiating device address, location, device type, floor level where applicable and status including indication of normal, alarm, trouble and supervisory status, as appropriate. |
| 8/11/2025 | Transfer | Firealarm22 | Fire alarm Notes 1 | Fire Alarm Notes: | | 8/8/2025 Fire alarm inspection started at 5 am. Mark Panilo and Bart Meinhardt onsite, 4 hours of overtime. |
| 8/11/2025 | Transfer | Firealarm14 | Correction(s) #1 | <div>Correct the following item(s):</div><div><br></div> | | Tanana Child Development Center was required to have full smoke detection in the facility and hallway outside the facility leading to the smoke protected atrium as shown on permit F17-1111 as part of the buildout of permit C17-1399. This need to be maintained per 2018 International Existing Building Code (IEBC) 104.10. |
| 8/11/2025 | Transfer | Firealarm15 | Correction(s) #2 | <div>Correct the following item(s):</div><div><br></div> | | There are additional smoke control systems in the building that are not connected to the building fire alarm system. East and West Stairwells have stairwell pressurization that need to be connected to the fire alarm for control of ASU-4. <div><br></div><div>North (ASU-1) and South (ASU-2) buildings have smoke control that needs to be connected to the fire alarm system. Sequencing on the smoke control system needs to be determined by the engineer. It is suspected that when the atrium smoke control system activated that ASU 1 and 2 activated to create a positive pressure system in the north and south building while the atrium went negative pressure. 2018 IFC 909.12.3 and 909.12.4</div> |