Inspection #: 827915
Inspection Type: Final Plumbing
Inspector: E.Wood
Result: Correction
Comment: See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/11/2025CorrectedPlumbFinalCommentsSee Inspector CommentsEQ-5 retarder next to the garage door.Per the 2018 UPC 402.8 the retarder needs to be drained to an approved location per the manufacturer's installation instructions.
4/11/2025CorrectedPlumbFinalCommentsSee Inspector CommentsThere appears to be a floor sink without drainage connecting to it.Per the 2018 UPC 1007.1 "Floor drain or similar traps directly connected to the drainage system and subject to infrequent use shall be protected with a trap seal primer."
4/11/2025CorrectedPlumbFinalCommentsSee Inspector CommentsVarious appliances that are using water to create steam, and/ or coffee, espresso etc..Backflow prevention shall be provided for various appliances per the 2018 UPC table 603.2.
4/11/2025TransferPlumbFinalCommentsSee Inspector CommentsPlans.Plans shall reflect the work being performed. Backflow protection is not shown, and water to the EQ - gas deck oven and a coffee machine is not shown, there may be more.
4/11/2025CorrectedPlumbFinalCommentsSee Inspector CommentsAll gas fired appliances with casters.Per the 2018 UPC 1212.1.2 "Movement of appliances with casters shall be limited by a restraining device installed in accordance with the connector and appliance manufacturer's installation instructions."