Date | Status | Code | Description | Ref | Location | Comments |
4/11/2025 | Corrected | PlumbFinal | Comments | See Inspector Comments | EQ-5 retarder next to the garage door. | Per the 2018 UPC 402.8 the retarder needs to be drained to an approved location per the manufacturer's installation instructions. |
4/11/2025 | Corrected | PlumbFinal | Comments | See Inspector Comments | There appears to be a floor sink without drainage connecting to it. | Per the 2018 UPC 1007.1 "Floor drain or similar traps directly connected to the drainage system and subject to infrequent use shall be protected with a trap seal primer." |
4/11/2025 | Corrected | PlumbFinal | Comments | See Inspector Comments | Various appliances that are using water to create steam, and/ or coffee, espresso etc.. | Backflow prevention shall be provided for various appliances per the 2018 UPC table 603.2. |
4/11/2025 | Transfer | PlumbFinal | Comments | See Inspector Comments | Plans. | Plans shall reflect the work being performed. Backflow protection is not shown, and water to the EQ - gas deck oven and a coffee machine is not shown, there may be more. |
4/11/2025 | Corrected | PlumbFinal | Comments | See Inspector Comments | All gas fired appliances with casters. | Per the 2018 UPC 1212.1.2 "Movement of appliances with casters shall be limited by a restraining device installed in accordance with the connector and appliance manufacturer's installation instructions." |