Inspection #: 827906
Inspection Type: Final Mechanical
Inspector: E.Wood
Result: Correction
Comment: See corrections. CCO for FF&E until August 15, 2025. NOTES: #1. Refrigeration contractor needs to be added to the mechanical permit. This will become a correction on the next inspection. #2. Refrigeration piping and equipment will need to be tested and inspected. #3. The new RTU has a circuit board that is bad from the factory. Once the board is replaced ( it's on the way) we will need to see it functionPER T.WOODS. OK FOR FULL CCO UNTIL 8/15/25 (SEE PLUMBING INSPECTION COMMENTS FOR FF&E REQUIREMENTS) - RED

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/10/2025TransferMechFinalSee commentsSee Inspector CommentsPlansDiffered submittals, stamped approved by the plan reviewer, are required for the new type 1 hood showing the attachment of the hood
4/9/2025TransferMechFinalSee commentsSee Inspector CommentsThe roof.Per 306.5 Where equipment requiring access or appliances are located on an elevated structure or roof of a building, such access shall not require climbing over obstructions greater than 30" in height. Access to both the make up air unit and the RTU need a permanently affixed ladder or stairs.
4/9/2025TransferMechFinalSee commentsSee Inspector CommentsThe roof.Per the 2018 IMC 304.11, "Guards shall be provided where various components that require service and roof hatch openings are located within 10 feet of a roof edge or open side of a walking surface and such edge or open side is located more than 30" above the floor, roof, or grade below." Both the RTU, and the make up air require guards.
4/9/2025TransferMechFinalSee commentsSee Inspector CommentsThe project.Per the admin. code, prints shall reflect the work being performed. A deviation from the blue prints shall require a change order submitted to the MOA, approved and stamped by the plan reviewer. This stamped, approved, change order shall be on site at the time of inspection. The AC equipment for the "little sisters area" has been removed from the scope, therefore a change order is required.