Inspection #: 827702
Inspection Type: Electrical Temporary
Inspector: M.Green
Result: Correction
Comment: Fire Island Bakery addition. Contractor wants to energize new 400A service on building. Not allowable because:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/11/2024TransferCorrect following Item  New service disconnect.Fuses not installed. Disconnect not feeding a load at this time.
10/11/2024TransferCorrect following Item  Existing service.Still energized. Will not green tag new service with existing service energized.
10/11/2024TransferCorrect following Item  Approved drawings.Not on site. Probably none available because permit still open.
10/11/2024TransferCorrect following Item  Permit.Still open. Will not energize permanent service on temp inspection.