| Date | Status | Code | Description | Ref | Location | Comments |
| 1/27/2025 | Transfer | Correct Below | * | | Small magnetically held bar table lights. | No instructions on site. Cords are installed concealed in a cavity under table top. |
| 1/27/2025 | Transfer | Correct Below | * | | Goose-neck luminaires on small tables. | 1. Cannot pull individual conductors through wood chase. 2. Mounting screws provided appear to be too short for the situation. 3. Appears to be missing a J-box for terminations. 4. No instructions on site. |
| 1/27/2025 | Transfer | Correct Below | * | | Small table cords. | 1. Will need proper termination devices for fine stranded conductors. 2. Verify proper circuit OCPD for #14 cord. |
| 1/27/2025 | Transfer | Correct Below | * | | Aircraft cable hung strip fixture in sheetrock ceiling section. | Requires access hatch to make boxes accessible. |
| 1/27/2025 | Transfer | Correct Below | * | | Aircraft cable hung strip lights over tables. | Class 2 driver is remote from the fixture. Short section of flex from driver does not completely cover the cable / cord. Show instructions. If instructions permit class 2 cable without raceway protection, show that cable / cord is plenum rated. |
| 9/30/2024 | Transfer | Correct Below | * | | Office C3441C | light missing. |
| 9/30/2024 | Transfer | Correct Below | * | | Storage C3441C | new panel. Post AFC and date, along with panel schedule. |