Inspection #: 826991
Inspection Type: Plumbing Rough
Inspector: N.Jackson
Result: Correction
Comment: Plumbing Rough and Test Partial Pass. See Corrections. Natural Gas Rough and Tests approved for risers & branches serving rooms# 404, 402, 424, 426, 432, 434. Test for room# 436 failed. Area inspected is on the North side of the West wing.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/4/2024CorrectedGasPipeRgh4Gas Test FailedGas test failed - UPC local amendment 1214.3.2Riser related to room# 436Leak detected on piping, gauge broken.
9/9/2024TransferPlumbRgh14CommentsSee Inspectors CommentsWater pipingAs per 2018 UPC 609.10 hammer arrestors required.
7/18/2024TransferPlumbRgh14CommentsSee Inspectors Comments Cleanouts required for WC and most sinks. All drain lines on 1st floor beyond 5 feet from main require a cleanout. THIS IS FOR ENTIRE FIRST FLOOR